PRODUCTS
Four products that work together as a complete air quality system, or alongside the plant you already have.
THE RANGE
Everything from plant to floor tile

DELIVERS THE AIR
Floor-tile Unit
VFU
The intelligent floor tile that controls local temperature by regulating how much conditioned air enters the room.
Versions
Standard and Compact
Floor void
Standard from 230 mm, Compact from 150 mm
Fans
Two variable-speed DC fans
Damper
0–10 Vdc modulating, adjustable minimum
Extras
Optional electric heater, RS485 and NFC set-up
Download the brochure

CONDITIONS THE AIR
Air Centre
VAC
A low-noise downflow air handling unit that filters and conditions return air and supplies it to the floor void.
Design
Four-pipe, separate cooling and heating
Location
Perimeter riser cupboards or enclosures
Filtration
G4 as standard, M5 or F7 optional
Coils
Chilled water and low-pressure hot water
Connectivity
RS485 to the Control System
Download the brochure

MONITORS AND CONTROLS
Control System
VCS
A central controller, room interfaces and IAQ sensors that join the whole system together.
Controller
10-inch touch screen
BMS links
Modbus RTU, BACnet TCP/IP, BACnet MSTP
Sensors
Temperature, humidity, CO₂, VOCs, PM10, PM2.5
Functions
Time clock, setpoints, CO₂ purge control
Download the brochure

SUPPLIES THE WATER
Water Centre
VWC
High-efficiency heat pumps and coolers that supply chilled and hot water to the system.
Heat pumps
Air source and water source
Options
2-pipe reversible or 4-pipe multifunction
Refrigerants
Low-GWP A1 and A2L, including R744 and R290
Coolers
Dry and adiabatic, flat-bed and V-bank
Download the brochure
CHOOSING A TILE
Standard or Compact?
The deciding factor is floor void depth. Both versions share the same features and the same acoustic performance.
Standard
230 mm+
For regular floor voids. Delivers greater air volumes, up to 158 l/s at NR35, with specific fan power of 0.09 W/l/s.
Get the performance data
Compact
150 mm+
For shallower floor voids. Delivers slightly lower air volumes, 100 l/s at NR35, with specific fan power of 0.15 W/l/s.
Get the performance data
OPTIONS
Configured to the project
Electric heater
Optional on the floor-tile unit, for when floor void air needs a boost or central heating is unavailable.
Enhanced filtration
M5 or F7 filters can replace the standard G4 panel filters in the Air Centre.
Room interfaces
Desk or wall-mounted controls with built-in temperature, humidity and CO₂ sensing.
Refrigerant choices
Low-GWP A1 and A2L options on heat pumps, including CO₂ (R744) and propane (R290).
OPEN BY DESIGN
Use the full system, or the parts you need
The Control System is not limited to the VersaTile Air Centre. Any local or central cooling, heating or AHU plant that uses Modbus can connect to the controls, IAQ sensors and floor-tile units.
Third-party plant
Chiller
Heating plant
AHU
Modbus
VersaTile Control System
IAQ sensors
Floor-tile units
Not sure which products you need?